We have ruined two electric blankets using a MSW inverter. At that time, we didn't know it was a problem. We have since switched to a pure syne wave inverter. No more issues!

Expand full comment
brian's avatar

Where is the twist lock in that ? The product just looks like it plugs into a NEMA 10-50R (3 wire range) and converts it to a 14-50R (4 wire range/RV/Tesla). The 10-50R uses the same conductor for neutral and ground which was allowed (with certain conditions) for many years, (not like a 6-50R welder outlet which has no neutral) Mike, have you verified that the ground is actually floating or is it possible that the ground and neutral on the 14-50 side are tied together? If so, it would be not much different than wiring a 14-50R to your main service. Not saying the adapter is a good idea, but I am really curious if they really floated the ground as one reviewer claims.